Breaker keeps tripping?
Find why your breaker trips, safely, and what that circuit can carry.
A breaker that trips after a few minutes with a heater, hair dryer, microwave or kettle on is overloaded: a 15 A circuit carries 1,800 W at most (15 A × 120 V) and about 1,440 W (80%) for anything that runs a while, so one 1,500 W space heater uses 83% of it by itself. A 20 A circuit carries 2,400 W, or 1,920 W at 80%. A breaker that trips the moment you reset it, even with everything unplugged, has a short or a ground fault: leave it off and call an electrician; one that trips only when one thing is plugged in has found a faulty appliance. A burning smell, scorch marks, a hot or buzzing breaker or panel, or water near the panel: don't reset it, and call an electrician.
Every question and every fix
Before you reset it: do you notice any of these?
Stop: Don't reset it: call an electrician
Heat, a smell or buzzing at the panel or a breaker means a connection is overheating. Resetting it can start a fire.
- Smoke or flame: get everyone out and call 911 from outside.
- Don't touch the panel.
- Call an electrician now.
Call an electrician.
Stop: Stay away from a wet panel
Water at the panel can make its metal live. Don't touch it, and don't stand in water near it.
- Keep everyone away.
- Call the electric utility to cut the power, and an electrician to check the panel before it's used.
Call the utility and an electrician.
Stop: Have an electrician look at this panel
Federal Pacific (Stab-Lok) and Zinsco panels are widely flagged by home inspectors: in tests, many Federal Pacific breakers failed to trip on overload, and Zinsco breakers can arc where they meet the bus.
- Don't keep resetting breakers in it.
- Don't open the cover.
- Have a licensed electrician evaluate it; many replace these panels.
Call an electrician.
When does it trip?
Try this first
- To reset: push the handle all the way to OFF until it clicks, then back to ON (Square D, Eaton, Siemens).
Stop: It trips again at once: there's a fault
A breaker that trips the moment you reset it, with things unplugged, is seeing a short or a ground fault in the wiring or a device on the wall. Resetting it again and again can cause an arc flash.
- Leave the breaker OFF. Don't hold it on or tape it.
- Write down which breaker it is, and any light it showed.
- Look (don't touch) for blackened plugs, outlets or switches on that circuit and tell the electrician.
- Call an electrician (Siemens: "a fault still exists on the circuit").
Call an electrician.
Too much on one circuit
Why: A breaker that trips after a few minutes with something big running is overloaded: its thermal part heats up and trips, sooner the bigger the overload. A 1,500 W heater alone uses 83% of a 15 A circuit.
- Turn off or unplug the big things on that circuit, then reset the breaker.
- Add up what runs at once with the load check below. Aim to stay under 80% of the breaker for anything that runs a long time.
- Move a heater, kettle or hair dryer to an outlet on another circuit. To map a circuit, switch its breaker off and note which outlets go dead.
- Plug heaters straight into a wall outlet: never an extension cord or a power strip (Lasko, USFA).
- Never put in a bigger breaker: the wire is sized to the breaker it has, and a bigger one lets it overheat.
What happened when you unplugged everything?
Try this first
- With the breaker OFF, look at the plugs and outlets on that circuit: blackened ones mean stop and call an electrician (Siemens).
- Check for loose bulbs and pinched or damaged cords.
- Unplug everything on the circuit, reset the breaker, then plug things back in one at a time.
Something plugged in is the problem
Why: When the GFCI or breaker holds until one thing is plugged back in, that thing leaks current to ground or has a short. It's the appliance, not the wiring.
- Retire it, or have it repaired. Don't move it to another outlet to "see if it works there".
- Check its cord and plug for damage, and the outlet it was in for blackening.
- Plug the rest back in one at a time, testing as you go.
Watch for a pattern
Why: A breaker that trips now and then with nothing big running can be a loose connection that heats up, a failing breaker, or an appliance that leaks only sometimes.
- Write down when it trips and what was running, for a week.
- If it lines up with one appliance (a fridge or a freezer starting, a vacuum), that appliance is the suspect.
- If there's no pattern, or it's happening more often, have an electrician check the connections on that circuit: loose ones cause most nuisance trips (Siemens).
What does it show?
AFCI and GFCI breakers have a Test button, and many have a light that shows the last trip. Brands differ: read the label on the breaker or the panel door. Siemens shows the last trip for 5 seconds when you turn it on.
Stop: The breaker itself needs replacing
A breaker that won't trip when you press its Test button, or that blinks its replace code (Siemens GFCI: blinking; Square D: 7 pulses), can no longer protect the circuit. Replacing it means working inside the panel.
- Write down the breaker's brand, size and code.
- Use that circuit as little as you can until it's replaced.
- Call an electrician.
Call an electrician.
Check the load
Everything that runs at once on one breaker. The breaker's size is printed on its handle.
What can a 15 or 20 amp circuit run at once?
Watts = amps × 120 V. Stay under the 80% line for anything that runs a while (a heater, an AC), and never put in a bigger breaker: the wire in the wall is sized for the one it has.
| Breaker | Trips above | 80% line | Wire |
|---|---|---|---|
| 15 A | 1,800 W | 1,440 W | 14-gauge copper |
| 20 A | 2,400 W | 1,920 W | 12-gauge copper |
| Appliance | Draws | Of 15 A | Of 20 A |
|---|---|---|---|
| Space heater | 1,500 W | 83% | 63% |
| Hair dryer | 1,875 W | 104% | 78% |
| Clothes iron | 1,800 W | 100% | 75% |
| Microwave | 1,500 W | 83% | 63% |
| Electric kettle | 1,500 W | 83% | 63% |
| Air fryer | 1,700 W | 94% | 71% |
| Toaster | 1,400 W | 78% | 58% |
| Coffee maker | 1,200 W | 67% | 50% |
| Vacuum | 1,440 W | 80% | 60% |
| Window AC, 12,000 BTU | 1,115 W | 62% | 46% |
| Portable AC | 1,365 W | 76% | 57% |
| Dehumidifier | 595 W | 33% | 25% |
Your appliance's label wins. A microwave draws more than its cooking watts: a "1,100 W" one draws about 1,500 W.
Will a space heater and a hair dryer trip a 15 A breaker?
Yes. Together they draw almost twice what the circuit can carry.
- Add the watts: 1,500 W + 1,875 W = 3,375 W.
- Amps: 3,375 W ÷ 120 V = 28.1 A on a 15 A breaker (188% of it).
- That's over 1,800 W, so the breaker trips, usually within a few minutes.
- Move the hair dryer to another circuit: 1,500 W is left, still over the 1,440 W line, so the heater should have that circuit to itself.
Where the numbers come from
- The limit: watts = amps × 120 V. The 80% line is a planning rule for anything that runs a while: the code caps one plug-in appliance at 80% of its circuit (NEC 210.23) and sizes breakers for long loads at 125% (210.20).
- The watts: the Department of Energy's appliance list and makers' spec sheets (GE, Frigidaire, Midea, Cuisinart). Your appliance's label wins: use "Something else" for its number.
- Why it trips: a breaker's thermal part trips on an overload, sooner the bigger it is; its magnetic part trips at once on a short (IAEI, Siemens).
Typical watts
| Device | Draws |
|---|---|
| Space heater | 750–1,500 W |
| Hair dryer | 1,200–1,875 W |
| Microwave | 1,500–1,780 W drawn (a "1,100 W" one) |
| Electric kettle | 1,500 W |
| Air fryer | ~1,700 W |
| Toaster | 800–1,400 W |
| Coffee maker | 900–1,200 W |
| Clothes iron | 1,000–1,800 W |
| Vacuum | 1,000–1,440 W |
| Window AC, 12,000 BTU | 1,020–1,115 W |
| Portable AC | 1,200–1,365 W |
| Dehumidifier, 50 pint | 470–593 W |
Not yet reviewed by a licensed electrician. Your local code wins.
Questions people ask
Why does my breaker keep tripping?
Three usual causes. It trips after a few minutes with a heater, hair dryer, microwave or kettle on: too much on one circuit (an overload). It trips the moment you reset it, even with things unplugged: a short or a ground fault, so leave it off and call an electrician. It trips when one thing is plugged in: that appliance is faulty.
How many watts can a 15 amp circuit handle?
1,800 W at most (15 A × 120 V), and about 1,440 W (80%) for anything that runs a while. A 20 A circuit: 2,400 W, 1,920 W at 80%. One 1,500 W space heater uses 83% of a 15 A circuit by itself.
Can I plug a space heater into a power strip?
No. Heater makers (Lasko) and the U.S. Fire Administration say to plug space heaters straight into a wall outlet, never an extension cord or a power strip.
Should I put in a bigger breaker?
Never. The breaker protects the wire in the wall, which is sized for it: a 15 A breaker for 14-gauge copper, 20 A for 12-gauge. A bigger breaker lets the wire overheat.
What do the lights on an AFCI breaker mean?
Brands differ: read the label on the breaker or the panel door. Siemens shows the last trip type for 5 seconds when you turn it on; a blinking Siemens GFCI breaker, or 7 pulses on a Square D, means the breaker needs replacing, which is an electrician's job.