Shop reference
Wire gauge chart
The wire size for your amps and distance, and the breaker it takes.
In house wiring, 14 AWG copper is for a 15 amp breaker, 12 AWG for 20 amps and 10 AWG for 30 amps (NEC 240.4(D)). A 30 amp circuit, like an electric dryer or a water heater, takes 10 AWG copper (10/2 or 10/3 cable), or 8 AWG aluminum. On a long run, go up a size to keep the voltage drop under 3%: at a full 20 amps on 120 volts, 12 AWG copper reaches 3% at about 45 ft one way and 10 AWG at about 75 ft. Type your amps and the distance below for your wire.
The charts
The bare metal of a solid wire at 20 °C. Stranded wire of the same gauge has the same metal but is a little wider.
| AWG | Diameter in | mm | Area mm² | Circular mils | Ω / 1,000 ft (Cu) | Ω / 1,000 ft (Al) |
|---|---|---|---|---|---|---|
| 4/0 | .4600 | 11.684 | 107.2 | 211,600 | 0.04901 | 0.08035 |
| 3/0 | .4096 | 10.405 | 85.03 | 167,806 | 0.0618 | 0.1013 |
| 2/0 | .3648 | 9.266 | 67.43 | 133,077 | 0.07793 | 0.1278 |
| 1/0 | .3249 | 8.251 | 53.48 | 105,535 | 0.09827 | 0.1611 |
| 1 | .2893 | 7.348 | 42.41 | 83,693 | 0.1239 | 0.2031 |
| 2 | .2576 | 6.544 | 33.63 | 66,371 | 0.1563 | 0.2562 |
| 3 | .2294 | 5.827 | 26.67 | 52,635 | 0.197 | 0.323 |
| 4 | .2043 | 5.189 | 21.15 | 41,741 | 0.2485 | 0.4073 |
| 5 | .1819 | 4.621 | 16.77 | 33,102 | 0.3133 | 0.5136 |
| 6 | .1620 | 4.115 | 13.3 | 26,251 | 0.3951 | 0.6477 |
| 7 | .1443 | 3.665 | 10.55 | 20,818 | 0.4982 | – |
| 8 | .1285 | 3.264 | 8.366 | 16,510 | 0.6282 | – |
| 9 | .1144 | 2.906 | 6.634 | 13,093 | 0.7921 | – |
| 10 | .1019 | 2.588 | 5.261 | 10,383 | 0.9988 | – |
| 11 | .0907 | 2.305 | 4.172 | 8,234 | 1.26 | – |
| 12 | .0808 | 2.053 | 3.309 | 6,530 | 1.588 | – |
| 13 | .0720 | 1.828 | 2.624 | 5,178 | 2.003 | – |
| 14 | .0641 | 1.628 | 2.081 | 4,107 | 2.525 | – |
| 15 | .0571 | 1.450 | 1.65 | 3,257 | 3.184 | – |
| 16 | .0508 | 1.291 | 1.309 | 2,583 | 4.015 | – |
| 17 | .0453 | 1.150 | 1.038 | 2,048 | 5.063 | – |
| 18 | .0403 | 1.024 | 0.823 | 1,624 | 6.385 | – |
| 19 | .0359 | 0.912 | 0.6527 | 1,288 | 8.051 | – |
| 20 | .0320 | 0.812 | 0.5176 | 1,022 | 10.15 | – |
| 21 | .0285 | 0.723 | 0.4105 | 810 | 12.8 | – |
| 22 | .0254 | 0.644 | 0.3255 | 642 | 16.14 | – |
| 23 | .0226 | 0.573 | 0.2582 | 509 | 20.36 | – |
| 24 | .0201 | 0.511 | 0.2047 | 404 | 25.67 | – |
| 25 | .0179 | 0.455 | 0.1624 | 320 | 32.37 | – |
| 26 | .0159 | 0.405 | 0.1288 | 254 | 40.81 | – |
| 27 | .0142 | 0.361 | 0.1021 | 202 | 51.47 | – |
| 28 | .0126 | 0.321 | 0.08098 | 160 | 64.9 | – |
| 29 | .0113 | 0.286 | 0.06422 | 127 | 81.83 | – |
| 30 | .0100 | 0.255 | 0.05093 | 101 | 103.2 | – |
| 31 | .0089 | 0.227 | 0.04039 | 80 | 130.1 | – |
| 32 | .0080 | 0.202 | 0.03203 | 63 | 164.1 | – |
| 33 | .0071 | 0.180 | 0.0254 | 50 | 206.9 | – |
| 34 | .0063 | 0.160 | 0.02014 | 40 | 260.9 | – |
| 35 | .0056 | 0.143 | 0.01597 | 32 | 329 | – |
| 36 | .0050 | 0.127 | 0.01267 | 25 | 414.8 | – |
| 37 | .0045 | 0.113 | 0.01005 | 20 | 523.1 | – |
| 38 | .0040 | 0.101 | 0.007967 | 16 | 659.6 | – |
| 39 | .0035 | 0.090 | 0.006318 | 12 | 831.8 | – |
| 40 | .0031 | 0.080 | 0.00501 | 10 | 1049 | – |
NEC 2023 Table 310.16: up to 3 current-carrying wires together, 86 °F air. House cable (NM-B) uses the 60 °C column. * 240.4(D) caps the breaker below the table for 14, 12 and 10 AWG.
| Size | Cu 60 °C | Cu 75 °C | Cu 90 °C | Al 60 °C | Al 75 °C | Al 90 °C | Breaker, at most |
|---|---|---|---|---|---|---|---|
| 14 | 15 A* | 20 A | 25 A | – | – | – | Cu 15 A |
| 12 | 20 A* | 25 A | 30 A | 15 A* | 20 A | 25 A | Cu 20 A · Al 15 A |
| 10 | 30 A* | 35 A | 40 A | 25 A* | 30 A | 35 A | Cu 30 A · Al 25 A |
| 8 | 40 A | 50 A | 55 A | 35 A | 40 A | 45 A | by the table |
| 6 | 55 A | 65 A | 75 A | 40 A | 50 A | 55 A | by the table |
| 4 | 70 A | 85 A | 95 A | 55 A | 65 A | 75 A | by the table |
| 3 | 85 A | 100 A | 115 A | 65 A | 75 A | 85 A | by the table |
| 2 | 95 A | 115 A | 130 A | 75 A | 90 A | 100 A | by the table |
| 1 | 110 A | 130 A | 145 A | 85 A | 100 A | 115 A | by the table |
| 1/0 | 125 A | 150 A | 170 A | 100 A | 120 A | 135 A | by the table |
| 2/0 | 145 A | 175 A | 195 A | 115 A | 135 A | 150 A | by the table |
| 3/0 | 165 A | 200 A | 225 A | 130 A | 155 A | 175 A | by the table |
| 4/0 | 195 A | 230 A | 260 A | 150 A | 180 A | 205 A | by the table |
| 250 kcmil | 215 A | 255 A | 290 A | 170 A | 205 A | 230 A | by the table |
| 300 kcmil | 240 A | 285 A | 320 A | 195 A | 230 A | 260 A | by the table |
| 350 kcmil | 260 A | 310 A | 350 A | 210 A | 250 A | 280 A | by the table |
| 400 kcmil | 280 A | 335 A | 380 A | 225 A | 270 A | 305 A | by the table |
| 500 kcmil | 320 A | 380 A | 430 A | 260 A | 310 A | 350 A | by the table |
Copper NM-B unless said. An appliance's label (minimum circuit amps, maximum breaker) wins.
| Circuit | Breaker | Copper wire | Cable | Why |
|---|---|---|---|---|
| Lights and outlets | 15 A | 14 AWG | 14/2 white | 240.4(D) |
| Outlets (most rooms) | 20 A | 12 AWG | 12/2 yellow | 240.4(D) |
| Kitchen counter, bath, laundry, garage outlets | 20 A | 12 AWG | 12/2 yellow | 210.11(C): 20 A circuits |
| Dishwasher, disposal, microwave | 20 A | 12 AWG | 12/2 yellow | maker's label (often 15–20 A) |
| Electric dryer | 30 A | 10 AWG | 10/3 pink | 240.4(D), a 4-wire hookup |
| Electric water heater (4,500 W) | 30 A | 10 AWG | 10/2 orange | 18.75 A × 125% = 23.4 A |
| Electric range or cooktop | 40 A | 8 AWG | 8/3 black | or 50 A on 6 AWG, per the label |
| Central A/C or heat pump | label | label | – | the unit's nameplate (MCA and max breaker) |
| EV charger, 32 A | 40 A | 8 AWG | 8/2 black | 625.41: breaker 125% of the charger |
| EV charger, 40 A | 50 A | 6 AWG | 6/2 black | 625.41 |
| EV charger, 48 A | 60 A | 4 AWG | 4 NM-B, or 6 THHN in conduit | 625.41 (hardwired) |
Add up the amps of everything on the cord; length is all the cords end to end. In doubt, go one gauge heavier. Never lighter than 16 AWG (CPSC).
| Tool amps | 25 ft | 50 ft | 100 ft | 150 ft |
|---|---|---|---|---|
| up to 6 A | 18 AWG | 16 AWG | 16 AWG | 14 AWG |
| 6–10 A | 18 AWG | 16 AWG | 14 AWG | 12 AWG |
| 10–12 A | 16 AWG | 16 AWG | 14 AWG | 12 AWG |
| 12–16 A | 14 AWG | 12 AWG | not recommended | not recommended |
NEC Table 310.12: only for the service or feeder that carries the whole house (the 83% rule). Not for a subpanel. The 2026 NEC changes this section: check what your town uses.
| Service | Copper | Aluminum |
|---|---|---|
| 100 A | 4 AWG | 2 AWG |
| 110 A | 3 AWG | 1 AWG |
| 125 A | 2 AWG | 1/0 AWG |
| 150 A | 1 AWG | 2/0 AWG |
| 175 A | 1/0 AWG | 3/0 AWG |
| 200 A | 2/0 AWG | 4/0 AWG |
| 225 A | 3/0 AWG | 250 kcmil |
| 250 A | 4/0 AWG | 300 kcmil |
| 300 A | 250 AWG | 350 kcmil |
| 350 A | 350 AWG | 500 kcmil |
| 400 A | 400 AWG | 600 kcmil |
How to read it
- The gauge (AWG) gets thicker as the number gets smaller: 14 is thinner than 12, and after 1 come 1/0, 2/0, 3/0 and 4/0. Every 3 gauges doubles the copper.
- Ampacity is how much current a wire carries without overheating. House cable (NM-B, "Romex") is held to the 60 °C column; single wires in conduit (THHN) to the 75 °C column, where the breaker and outlets are rated for it.
- The breaker protects the wire, so it can never be bigger than the wire allows: 14 AWG copper takes at most 15 A, 12 AWG 20 A, 10 AWG 30 A (NEC 240.4(D)).
- Voltage drop grows with distance. The NEC suggests no more than 3% on a branch circuit (a note, not a rule). Long runs get a bigger wire.
voltage drop = 2 × K × amps × feet ÷ circular mils K = 12.9 copper · 21.2 aluminum (feet one way) 15 A, 100 ft, 14 AWG: 2 × 12.9 × 15 × 100 ÷ 4,110 = 9.4 V (7.8%)
The numbers we use
- Sizes
- ASTM B258: d = 0.005 in × 92^((36 − n)/39)
- Resistance
- at 20 °C, annealed copper (100% IACS) and EC aluminum
- Ampacity
- NEC 2023 Table 310.16 (≤ 3 wires, 86 °F air)
- Breaker limits
- NEC 240.4(D)
- House cable
- NM-B at 60 °C (NEC 334.80)
- Services
- NEC Table 310.12, the whole house only
- Cords
- power-tool makers' cord table; CPSC: at least 16 AWG
- Cable colors
- the NM-B jacket code (3-wire colors from 2024); read the print on the jacket
This is a reference, not an electrical design. Local code wins: check the edition your town uses, and the appliance's own label (its minimum circuit amps and maximum breaker).
Questions people ask
What size wire for a 20 amp circuit?
12 AWG copper (12/2 NM-B, the yellow cable). The NEC limits 12 AWG copper to a 20 A breaker (240.4(D)). In aluminum it is 10 AWG.
What size wire for 30 amps?
10 AWG copper: 10/2 NM-B (orange) for a water heater, 10/3 for a dryer. 10 AWG copper can take up to a 30 A breaker.
Can I put 14 gauge wire on a 20 amp breaker?
No. 14 AWG copper is limited to a 15 A breaker (NEC 240.4(D)). A 20 A breaker on 14 AWG lets the wire overheat before the breaker trips. Use a 15 A breaker, or 12 AWG wire.
How far can you run 12 gauge wire on a 20 amp circuit?
At a full 20 A on 120 V, about 46 ft one way keeps the voltage drop under the 3% the NEC suggests. Most circuits carry much less than their breaker, so put in your real load: at 10 A the same wire goes about 90 ft.
What size wire for a 200 amp service?
2/0 copper or 4/0 aluminum, when the service carries the whole house (NEC Table 310.12, the 83% rule). A feeder to a subpanel is not sized this way.
What gauge extension cord do I need?
It depends on the tool's amps and the cord's length: a 12 A saw needs 16 AWG at 50 ft and 14 AWG at 100 ft. A 12–16 A tool needs 14 AWG at 25 ft and 12 AWG at 50 ft, and no longer cord. Never use lighter than 16 AWG (CPSC).