In house wiring, 14 AWG copper is for a 15 amp breaker, 12 AWG for 20 amps and 10 AWG for 30 amps (NEC 240.4(D)). A 30 amp circuit, like an electric dryer or a water heater, takes 10 AWG copper (10/2 or 10/3 cable), or 8 AWG aluminum. On a long run, go up a size to keep the voltage drop under 3%: at a full 20 amps on 120 volts, 12 AWG copper reaches 3% at about 45 ft one way and 10 AWG at about 75 ft. Type your amps and the distance below for your wire.

Updated · NEC 2023 Table 310.16 and 240.4(D) · Not yet reviewed by a licensed electrician; your local code wins

Find a wire

The charts

The bare metal of a solid wire at 20 °C. Stranded wire of the same gauge has the same metal but is a little wider.

Sizes
AWGDiameter inmmArea mm²Circular milsΩ / 1,000 ft (Cu)Ω / 1,000 ft (Al)
4/0.460011.684107.2211,6000.049010.08035
3/0.409610.40585.03167,8060.06180.1013
2/0.36489.26667.43133,0770.077930.1278
1/0.32498.25153.48105,5350.098270.1611
1.28937.34842.4183,6930.12390.2031
2.25766.54433.6366,3710.15630.2562
3.22945.82726.6752,6350.1970.323
4.20435.18921.1541,7410.24850.4073
5.18194.62116.7733,1020.31330.5136
6.16204.11513.326,2510.39510.6477
7.14433.66510.5520,8180.4982–
8.12853.2648.36616,5100.6282–
9.11442.9066.63413,0930.7921–
10.10192.5885.26110,3830.9988–
11.09072.3054.1728,2341.26–
12.08082.0533.3096,5301.588–
13.07201.8282.6245,1782.003–
14.06411.6282.0814,1072.525–
15.05711.4501.653,2573.184–
16.05081.2911.3092,5834.015–
17.04531.1501.0382,0485.063–
18.04031.0240.8231,6246.385–
19.03590.9120.65271,2888.051–
20.03200.8120.51761,02210.15–
21.02850.7230.410581012.8–
22.02540.6440.325564216.14–
23.02260.5730.258250920.36–
24.02010.5110.204740425.67–
25.01790.4550.162432032.37–
26.01590.4050.128825440.81–
27.01420.3610.102120251.47–
28.01260.3210.0809816064.9–
29.01130.2860.0642212781.83–
30.01000.2550.05093101103.2–
31.00890.2270.0403980130.1–
32.00800.2020.0320363164.1–
33.00710.1800.025450206.9–
34.00630.1600.0201440260.9–
35.00560.1430.0159732329–
36.00500.1270.0126725414.8–
37.00450.1130.0100520523.1–
38.00400.1010.00796716659.6–
39.00350.0900.00631812831.8–
40.00310.0800.00501101049–

How to read it

  1. The gauge (AWG) gets thicker as the number gets smaller: 14 is thinner than 12, and after 1 come 1/0, 2/0, 3/0 and 4/0. Every 3 gauges doubles the copper.
  2. Ampacity is how much current a wire carries without overheating. House cable (NM-B, "Romex") is held to the 60 °C column; single wires in conduit (THHN) to the 75 °C column, where the breaker and outlets are rated for it.
  3. The breaker protects the wire, so it can never be bigger than the wire allows: 14 AWG copper takes at most 15 A, 12 AWG 20 A, 10 AWG 30 A (NEC 240.4(D)).
  4. Voltage drop grows with distance. The NEC suggests no more than 3% on a branch circuit (a note, not a rule). Long runs get a bigger wire.
voltage drop = 2 × K × amps × feet ÷ circular mils
K = 12.9 copper · 21.2 aluminum   (feet one way)
15 A, 100 ft, 14 AWG: 2 × 12.9 × 15 × 100 ÷ 4,110 = 9.4 V (7.8%)

The numbers we use

Sizes
ASTM B258: d = 0.005 in × 92^((36 − n)/39)
Resistance
at 20 °C, annealed copper (100% IACS) and EC aluminum
Ampacity
NEC 2023 Table 310.16 (≤ 3 wires, 86 °F air)
Breaker limits
NEC 240.4(D)
House cable
NM-B at 60 °C (NEC 334.80)
Services
NEC Table 310.12, the whole house only
Cords
power-tool makers' cord table; CPSC: at least 16 AWG
Cable colors
the NM-B jacket code (3-wire colors from 2024); read the print on the jacket

This is a reference, not an electrical design. Local code wins: check the edition your town uses, and the appliance's own label (its minimum circuit amps and maximum breaker).

Questions people ask

What size wire for a 20 amp circuit?

12 AWG copper (12/2 NM-B, the yellow cable). The NEC limits 12 AWG copper to a 20 A breaker (240.4(D)). In aluminum it is 10 AWG.

What size wire for 30 amps?

10 AWG copper: 10/2 NM-B (orange) for a water heater, 10/3 for a dryer. 10 AWG copper can take up to a 30 A breaker.

Can I put 14 gauge wire on a 20 amp breaker?

No. 14 AWG copper is limited to a 15 A breaker (NEC 240.4(D)). A 20 A breaker on 14 AWG lets the wire overheat before the breaker trips. Use a 15 A breaker, or 12 AWG wire.

How far can you run 12 gauge wire on a 20 amp circuit?

At a full 20 A on 120 V, about 46 ft one way keeps the voltage drop under the 3% the NEC suggests. Most circuits carry much less than their breaker, so put in your real load: at 10 A the same wire goes about 90 ft.

What size wire for a 200 amp service?

2/0 copper or 4/0 aluminum, when the service carries the whole house (NEC Table 310.12, the 83% rule). A feeder to a subpanel is not sized this way.

What gauge extension cord do I need?

It depends on the tool's amps and the cord's length: a 12 A saw needs 16 AWG at 50 ft and 14 AWG at 100 ft. A 12–16 A tool needs 14 AWG at 25 ft and 12 AWG at 50 ft, and no longer cord. Never use lighter than 16 AWG (CPSC).