Outlet not working or GFCI won't reset?

Get a dead outlet working again, safely, and know when to call an electrician.

A dead outlet is usually a tripped GFCI or breaker, not a broken outlet: a GFCI cuts power to itself and every outlet after it on the circuit, so the Reset button may be in another bathroom, the garage, a kitchen counter, outdoors or the basement. A GFCI that won't reset usually has no power reaching it (most made since 2003 won't reset without it, so check the breaker first) or something plugged in after it is leaking to ground. With nothing tripped, a three-light plug-in tester tells the rest apart: no lights means no power reaches the outlet, and any fault reading (open ground, open neutral, reversed) is an electrician's job. A burning smell, scorch marks, sparks, a warm or buzzing outlet, or water on it: don't test it, switch that circuit's breaker off if you can reach the panel standing somewhere dry, and call an electrician.

Updated · From Leviton, Eaton, Hubbell, Square D and Siemens guides, Klein's tester manuals and CPSC · Not yet reviewed by a licensed electrician

What's going on?

Every question and every fix

What do you notice at the outlet?

Stop: Turn that circuit off and call an electrician

A burning smell, scorch marks, sparks, or an outlet or plate that's warm or buzzing means a connection is overheating inside the wall. It can start a fire, and resetting or testing it makes it worse.

  • Smoke or flame: get everyone out and call 911 from outside.
  • Otherwise, if you can reach the panel standing somewhere dry, switch that room's breaker OFF and leave it off.
  • Don't plug anything into it, and don't pull a hot plug out with bare hands.
  • Call an electrician today.

Call an electrician.

Stop: Don't touch it while it's wet

Water and a live outlet can kill. Don't dry it with a hair dryer or plug anything in to test it.

  • Keep everyone away from the outlet and anything plugged into it.
  • Only if you can reach the panel standing on a dry floor: switch that circuit's breaker OFF.
  • Water from a leak or a flood: stop the water first, and keep the power off in that area.
  • A GFCI that got wet gets replaced, not dried out (Leviton): have an electrician check it and the box.

Call an electrician.

How much is dead?

Test with a lamp you know works, not the thing that stopped.

Did a switch bring it back?

Try this first

  1. Flip every wall switch in the room, then try the outlet again. One switch may run an outlet, or just its top or bottom half.

A wall switch runs it

Why: Many rooms have an outlet (often just the top or bottom half) wired to a wall switch, for a lamp.

  1. Leave that switch on for things that need constant power, or use the other half.
  2. Not sure which half: plug a lamp into each half and flip the switch.

Where is the dead outlet?

A GFCI cuts power to the outlets after it on the same circuit, so the Reset button can be in another room.

Did a GFCI reset bring it back?

Try this first

  1. Press Reset firmly on the GFCI in every bathroom, not just this one: one 20 A circuit may feed the outlets of several bathrooms, all behind the first GFCI (NEC 210.11).
  2. Then look in the panel for a breaker with a Test button (a GFCI breaker), and reset it like any breaker.

It was a tripped GFCI

Why: A GFCI cuts the power to itself and every outlet after it on the circuit when it senses a leak to ground, so a dead outlet can be fixed by a Reset button in another room.

  1. Label it: a strip of tape on the GFCI listing the outlets it powers saves the next hunt.
  2. If it trips again soon, unplug everything on it and add things back one at a time: the one that trips it is leaking (often an old appliance, or something outdoors and damp).
  3. Press its Test button once a month, then Reset (CPSC, ESFI). If Test doesn't cut the power, replace the GFCI.

What does the GFCI do now?

Try this first

  1. Unplug everything on the GFCI and on the outlets after it.
  2. Press Reset firmly until it clicks.

Something plugged in is the problem

Why: When the GFCI or breaker holds until one thing is plugged back in, that thing leaks current to ground or has a short. It's the appliance, not the wiring.

  1. Retire it, or have it repaired. Don't move it to another outlet to "see if it works there".
  2. Check its cord and plug for damage, and the outlet it was in for blackening.
  3. Plug the rest back in one at a time, testing as you go.

Is its breaker on?

Most GFCIs made since 2003 won't reset without power reaching them.

Try this first

  1. In the panel, push any breaker that isn't lined up fully OFF, then ON.
  2. Press Reset on the GFCI again.

It was the breaker

Why: A breaker trips when the circuit draws too much or sees a fault, and sits in the middle until it's reset.

  1. Note which breaker it was and what was running when it tripped.
  2. If it trips again with a heater, hair dryer, microwave or kettle on, the circuit is overloaded: check the load.
  3. If it trips again with little running, or right away, don't keep resetting it.

Stop: It trips again at once: there's a fault

A breaker that trips the moment you reset it, with things unplugged, is seeing a short or a ground fault in the wiring or a device on the wall. Resetting it again and again can cause an arc flash.

  • Leave the breaker OFF. Don't hold it on or tape it.
  • Write down which breaker it is, and any light it showed.
  • Look (don't touch) for blackened plugs, outlets or switches on that circuit and tell the electrician.
  • Call an electrician (Siemens: "a fault still exists on the circuit").

Call an electrician.

Does a tester show power at the GFCI?

A tripped GFCI shows no power at its face. With a voltage pen held to its side slots, a beep means power reaches it.

Replace the GFCI

Why: A GFCI that won't reset with power reaching it and nothing plugged in, or shows a red light that won't clear, has failed. Most made since 2015 test themselves and lock out when they fail.

  1. Switch the breaker off and tape it. Test live, dead, live.
  2. Unscrew the GFCI and pull it out. Stop and call an electrician if you see: aluminum wire (dull silver, "AL" on the cable; CPSC), more than two cables in the box, scorched plastic or wire, no bare or green ground wire, or anything that doesn't match the old outlet.
  3. One cable in the box: it goes on the LINE terminals. Two cables: only if the old GFCI's wires are on terminals marked LINE and LOAD, move them to the same ones on the new GFCI. Unmarked or unsure: stop, an electrician.
  4. Bare or green to the green screw. Same rating: 15 A, or 20 A only on a 20 A circuit with 12-gauge wire.
  5. Fold the wires in, screw it up, breaker on. It should show green or reset; press Test, then Reset.
  6. Test it monthly (CPSC).

Parts: elec gfci 15 (or 20 A: see step 4), elec tester.

Stop: The break is before this outlet

When a run of outlets is dead with no breaker or GFCI tripped, a connection has come loose at the last outlet that still works, or inside a box you can't see. Finding it means opening live circuits one by one.

  • Leave those outlets unused.
  • Note which outlets are dead and which nearest ones still work.
  • Call an electrician: it's usually a short visit.

Call an electrician.

Test it first: a $15 tester

Why: Guessing at a dead outlet wastes time, and swapping one that has a wiring fault doesn't fix it. A plug-in tester tells you in a second.

  1. Get a three-light outlet tester with a GFCI button. It also tests your GFCIs.
  2. Check it on an outlet you know works.
  3. Plug it into each half of the dead outlet, read the chart on it, and come back here.

Parts: elec tester.

Is the red light flashing?

Brands differ: on Leviton a red light means a problem; on Hubbell a steady red just means tripped. A flashing red means replace it on every brand we checked.

Stop: A new GFCI that won't reset is usually wired backwards

GFCIs have LINE terminals (power in) and LOAD terminals (to the outlets after it). Swapped, most newer GFCIs refuse to reset; some older ones work but don't protect you. Telling the wires apart takes a meter.

  • Switch its breaker OFF.
  • Don't swap wires by guessing.
  • Have an electrician rewire it.

Call an electrician.

What does a plug-in tester show?

A three-light outlet tester plugs in like a lamp. Read its lights against the chart printed on it (Klein, Sperry): brands differ.

Try this first

  1. Check the tester on an outlet you know works first.
  2. Plug it into each half of the dead outlet.

Is there power nearby?

No lights means no power reaches the outlet. The break is at this outlet or at the one before it, often a loose push-in connection.

Replace the outlet, like for like

Why: The outlet itself has failed: worn contacts that drop plugs, a cracked face, or a push-in connection inside it that let go.

  1. Switch the breaker off and put tape over it.
  2. Test live, dead, live (the box above). Take the cover off and unscrew the outlet; pull it out by its ears without touching the wire ends.
  3. Stop and call an electrician if you see: aluminum wire (dull silver, "AL" on the cable; CPSC), more than two cables in the box, scorched plastic or wire, no bare or green ground wire, or anything that doesn't match the old outlet.
  4. Take a photo, then move each wire to the new outlet: black (hot) to a brass screw, white (neutral) to a silver screw, bare or green (ground) to the green screw. Use the side screws, wire looped clockwise, no insulation under the screw (Leviton), not the push-in holes (Siemens).
  5. Same rating: a 15 A outlet on a 15 A breaker; a 20 A outlet only on a 20 A breaker with 12-gauge copper wire. Tamper-resistant (required in homes since the 2008 code).
  6. In a kitchen, bathroom, garage, basement, laundry or outdoors it must be GFCI-protected: if no GFCI before it protects it, use a GFCI outlet instead.
  7. Fold the wires in, screw it up, cover on, breaker on. Test: the tester should read correct.
  8. The new outlet is dead too: the break is before it, in another box. Switch the breaker off again and call an electrician.

Many towns let you replace an outlet in your own home without a permit; some don't. Check with your building department.

Parts: elec outlet 15 (or 20 A: see step 5), elec plate, elec tester.

Stop: The tester found a wiring fault

An open ground, an open neutral or reversed wires won't fix themselves, and an outlet swap won't either: the fault is in the wiring, often a loose connection at another outlet.

  • Stop using that outlet, and the ones on its circuit if they act up too.
  • Write down the tester's lights and which outlets read the same.
  • Call an electrician.

Call an electrician.

Did a GFCI reset bring it back?

Try this first

  1. Press Reset on each GFCI along the counter: each counter circuit usually starts at its own GFCI.
  2. In an older kitchen, look behind the fridge or in a nearby room too: before 2011 a GFCI didn't have to be easy to reach.
  3. Then the panel: a breaker with a Test button.

Did a GFCI reset bring it back?

Try this first

  1. Outdoor and garage outlets are often wired through a GFCI somewhere else: try the GFCIs in the garage (by the door, behind a freezer), the basement and the bathrooms.
  2. Then the panel: a breaker with a Test button.
  3. Outdoors after rain: if the GFCI keeps tripping, let things dry for a day; don't dry the outlet yourself.

Did a GFCI reset bring it back?

Try this first

  1. Try the GFCIs near the panel, the sump pump, the laundry and the garage.
  2. Then the panel: a breaker with a Test button.

Did the breaker bring it back?

Try this first

  1. Homes wired since about 2002 put bedrooms, then living areas, on AFCI breakers (they have a Test button). They can trip only a little: look closely at each handle.
  2. Push any that isn't lined up all the way to OFF, then ON.

What did you find in the panel?

Try this first

  1. Open the panel door (not the metal cover behind it).
  2. Look for a breaker handle that isn't lined up with the others, sits in the middle, or shows a red or orange flag.
  3. Push it all the way to OFF until it clicks, then back to ON (Square D, Eaton, Siemens).

Stop: Have an electrician look at this panel

Federal Pacific (Stab-Lok) and Zinsco panels are widely flagged by home inspectors: in tests, many Federal Pacific breakers failed to trip on overload, and Zinsco breakers can arc where they meet the bus.

  • Don't keep resetting breakers in it.
  • Don't open the cover.
  • Have a licensed electrician evaluate it; many replace these panels.

Call an electrician.

Check for a power cut

Why: When nothing works anywhere, the power is usually off at the street, or the main breaker tripped.

  1. Look outside: are the neighbours' lights and streetlights off? Check your utility's outage map or app.
  2. If only your home is out, check the main breaker at the top of the panel: push it fully OFF, then ON.
  3. Main breaker on and still no power: call the utility. Don't take the panel cover off.

Where the GFCI hides

A GFCI cuts power to the outlets after it on the same circuit, so look for the Reset button here.

Outlet not working inLook for a tripped GFCI at
Bathroomthe GFCI in another bathroom: one 20 A circuit may feed several bathrooms (NEC 210.11), protected by the first
Outdoors, porch, patioa GFCI in the garage, the basement or a bathroom, or a GFCI breaker
Garageanother garage outlet (by the door, behind a freezer), the basement, or a GFCI breaker
Kitchen counteranother counter GFCI; in older kitchens behind the fridge
Basement, laundrynear the panel, the sump pump or the laundry
A newer homea GFCI or dual-function breaker in the panel (it has a Test button)

Read your outlet tester

The usual three-light layout, left to right. Your tester's own chart wins: brands differ (Klein, Sperry).

ReadingLightsWhat to do
CorrectWiring reads right. It doesn't prove a good ground (Klein): a "bootleg" ground reads correct too.
Open groundNo ground: stop, an electrician.
Open neutralThe neutral is broken upstream, often a loose connection: stop, an electrician.
Open hotNo power: check the breaker and the GFCIs first.
Hot / neutral reversedReversed polarity: stop, an electrician.
Hot / ground reversedDangerous: stop using it, an electrician.

Where the answers come from

  1. GFCIs: Leviton's lockout guide and light meanings, Eaton's and Hubbell's sheets, and the code's history (IAEI): bathrooms since 1975, garages 1978, kitchens and basements from 1987, laundry 2014.
  2. Breakers: Square D, Eaton and Siemens on resetting (fully off, then on) and what a trip that repeats means.
  3. Testers: Klein's RT210 and voltage-pen manuals, including what they can't tell you.
  4. The stops: CPSC (aluminum wiring, test GFCIs monthly), ESFI and This Old House (heat, sparks, smell).

You may

Reset
breakers and GFCIs
Unplug
things to find the one that trips it
Replace
an outlet or GFCI like for like, power off and tested
Never
open the panel, or work on live wires

Not yet reviewed by a licensed electrician. Your local code wins.

Questions people ask

Why is my outlet not working?

Usually a tripped GFCI or breaker, not a broken outlet. A GFCI cuts power to itself and every outlet after it on the circuit, so the Reset button can be in another room: a bathroom, the garage, the kitchen counter, outdoors or the basement. Then check the panel for a breaker sitting in the middle, and push it fully off, then on.

Why won't my GFCI reset?

Most GFCIs made since 2003 won't reset without power reaching them, so check the breaker first. Then unplug everything on it and on the outlets after it: something leaking to ground keeps tripping it. A GFCI that was just installed and won't reset is usually wired backwards (LINE and LOAD swapped), and one that still won't reset with power and nothing plugged in has failed.

What does the red light on a GFCI mean?

It depends on the brand. On Leviton, a red light means a problem (a failed self-test or lost protection). On Hubbell, a steady red light just means tripped. A flashing red light means replace the GFCI on every brand we checked. Read the legend on the outlet.

How do I read an outlet tester?

Check the tester on an outlet you know works, then plug it into each half of the dead one and match its lights to the chart printed on it: brands differ. A "correct" reading doesn't prove the ground is good (Klein), and any fault reading means call an electrician.

Can I replace an outlet myself?

Many homeowners do, like for like: the breaker off, tested dead (live, dead, live), the same rating, tamper-resistant, and GFCI where the code wants it. Stop and call an electrician for aluminum wire, more than two cables in the box, scorched wires, no ground wire, or a GFCI whose LINE and LOAD wires you can't tell apart. Some towns require a permit.