Calculator

AC size calculator

The BTU each room needs, the unit that fits, and the price.

At the store today

ENERGY STAR's room chart

For an 8 ft ceiling. Then −10% heavily shaded, +10% very sunny, +600 BTU per person over two, +4,000 BTU in a kitchen.

Room, sq ftBTU per hour
100–1505,000
150–2506,000
250–3007,000
300–3508,000
350–4009,000
400–45010,000
450–55012,000
550–70014,000
700–1,00018,000
1,000–1,20021,000
1,200–1,40023,000
1,400–1,50024,000
1,500–2,00030,000
2,000–2,50034,000

ENERGY STAR's chart sizes a window or room AC by floor area, for an 8 ft ceiling: 6,000 BTU for 150–250 sq ft, 8,000 BTU for 300–350 sq ft, 12,000 BTU for 450–550 sq ft and 18,000 BTU for 700–1,000 sq ft. Then take 10% off for a heavily shaded room, add 10% for a very sunny one, add 600 BTU for each person over two and 4,000 BTU for a kitchen. A mini-split head is sized at about 25 BTU per sq ft (Trane): a 300 sq ft room needs 7,500 BTU, so a 9,000 BTU head.

Updated · ENERGY STAR's room AC chart, Trane's 25 BTU per sq ft, NEC 440.62 · Not yet reviewed by a licensed HVAC tech

What size AC for my room?

An 8 ft ceiling, normal sun, two people. The window unit is the smallest common size that covers ENERGY STAR's number; the mini-split head is the next size up from 25 BTU per sq ft.

BTU by room size
RoomSq ftENERGY STAR BTUWindow unit, BTUMini-split head, BTU
10 × 10 ft1005,0005,0006,000
10 × 12 ft1205,0005,0006,000
12 × 12 ft1445,0005,0006,000
12 × 15 ft1806,0006,0006,000
14 × 16 ft2246,0006,0006,000
15 × 20 ft3008,0008,0009,000
16 × 20 ft3208,0008,0009,000
18 × 20 ft3609,00010,0009,000
20 × 20 ft40010,00010,00012,000
20 × 25 ft50012,00012,00015,000
25 × 28 ft70018,00018,00018,000
30 × 30 ft90018,00018,00024,000

What size AC for a sunny 15 × 20 living room?

Very sunny, usually four people in it, plugged into a 15 A outlet.

  1. Area: 15 × 20 = 300 sq ft. ENERGY STAR's chart: 8,000 BTU for 300–350 sq ft.
  2. Very sunny: 8,000 + 10% = 8,800 BTU.
  3. Two people over two: + 2 × 600 = 10,000 BTU. A 10,000 BTU window unit covers it.
  4. Power: about 10,000 ÷ 11 = 910 W, or 7.9 A at 115 V (the label wins).
  5. The outlet: on a 15 A circuit shared with lights and outlets the limit is 50%, 7.5 A, so 7.9 A is too much. On a 15 A circuit of its own the limit is 80%, 12 A: that works (NEC 440.62).

How we work it out

  1. One room: ENERGY STAR's chart for the room's square feet, then its adjustments (shade, sun, people, a kitchen). A ceiling over 8 ft scales it by height ÷ 8: that one is our assumption. We pick the smallest window unit that covers it.
  2. The outlet: a unit's watts are about its BTU ÷ 11 (near the federal minimum efficiency; the label wins), and a plug-in room AC may use 80% of a circuit it has alone, 50% of a shared one (NEC 440.62).
  3. A mini-split head: Trane's 25 BTU per sq ft, with the same adjustments, rounded up to the next head size (6k, 9k, 12k, 18k, 24k). The DIY kits come pre-charged, so no refrigerant work; the 240 V circuit is an electrician's.
  4. A whole house: we don't size it. The building code calls for an ACCA Manual J load calculation (IRC M1401.3). We check a quote instead: its square feet per ton against where published Manual J results land for a home of that age (DOE/NREL; DOE Building America; Energy Vanguard's 200+ calculations), allowing up to 25% over the load (ACCA Manual S, NYC HPD) and nudged about 2.7% per °F for hotter or milder summers (NOAA normal summer highs by ZIP). The age bands and the nudge are our judgment.

The numbers we use

Before 1980
450–1,000 sq ft per ton (DOE: a conventional Raleigh house, 460)
1980–2005
700–1,500 sq ft per ton
2006 on
1,000–2,200 sq ft per ton (DOE Building America: a 2009-code house, about 1,290 in Chicago and in Orlando)
Rule of thumb
400–600 sq ft per ton: what most contractors still use (FSEC survey), and why most systems are oversized by about 47% (ACEEE for ENERGY STAR)

A heat pump in a cold climate may be sized larger to heat: the Manual J and Manual S show that too.

Questions people ask

How many BTU do I need for my room?

Start from ENERGY STAR's chart: 150–250 sq ft takes about 6,000 BTU, 350–400 about 9,000, 450–550 about 12,000 and 700–1,000 about 18,000, for an 8 ft ceiling. Then take 10% off for a heavily shaded room, add 10% for a very sunny one, add 600 BTU for each person over two who's usually in it, and add 4,000 BTU for a kitchen.

What size mini-split do I need?

Trane uses about 25 BTU per square foot: a 6,000 BTU head for up to about 240 sq ft, 9,000 up to 360, 12,000 up to 480, 15,000 up to 600, 18,000 up to 720 and 24,000 up to 960. Size each room's head on its own; one outdoor unit can feed several heads. Trane advises not going more than half a ton over the room's load.

How many square feet does a ton of AC cool?

There's no honest single number. The old rule of 400 to 600 sq ft per ton oversizes most homes: in published Manual J calculations, homes came out between about 600 and 3,300 sq ft per ton, averaging around 1,200 to 1,400. Insulation, windows, air leaks and ducts matter more than the floor area, which is why the building code asks for a Manual J load calculation (IRC M1401.3).

Is a bigger air conditioner better?

No. An oversized AC cools the air in short bursts and shuts off before it has pulled the moisture out, so the house feels damp and clammy, and the on-off cycling wears it out sooner (ENERGY STAR, DOE). Ask the contractor for the Manual J load calculation behind the size they quote.

Can I plug a window AC into any outlet?

Check the unit's amps on its label. Under the electrical code (NEC 440.62) a plug-in room AC may use up to 80% of a circuit it has to itself, or only 50% of one that also feeds lights and other outlets: on a shared 15 A circuit that's 7.5 A. Units of 18,000 BTU and up usually need a 230 V outlet. Never use an extension cord.