How to wire an outlet
On an outlet, the black (hot) wire goes on a brass screw, the white (neutral) on a silver screw, and the bare or green on the green screw (UHMC). Use the screws or the back clamp: the push-in holes take only 14-gauge solid copper (Leviton). With two cables (more outlets after this one), join each color with a short pigtail to one screw so the next outlets don't depend on this one. A replacement should be tamper-resistant, and in a kitchen, bathroom, garage, basement, laundry or outdoors, GFCI-protected (NEC 406.4(D)).
One cable (the end of the line)
Outlet box
Two cables (more outlets after it)
Outlet box
Half switched by a wall switch
The brass tab between the two hot screws is broken off; the silver tab stays (UHMC).
Outlet box
Step by step
First
- Turn off the breaker. A wall switch off is not enough. Put tape or a note on the breaker so nobody turns it back on.
- Prove it's dead: check your tester on an outlet you know is live, test every wire in the box, then check the tester on the live outlet again (Klein). A voltage pen alone isn't proof: use a plug-in or two-probe tester where you can.
- Take a photo of the wires before you move any of them.
Then
- Plug a lamp into the top and then the bottom: turn breakers off until both halves are dead (Leviton).
- Pull the outlet out and count the cables.
- Black on brass, white on silver, bare on green (UHMC). Screws or the back clamp; the push-in holes are for 14-gauge solid copper only.
- If the old outlet had the brass tab broken off (a switched half), break the same tab on the new one with pliers. Never the silver tab.
- Use a tamper-resistant (TR) outlet; in a kitchen, bathroom, garage, basement, laundry or outdoors, a GFCI.
- Breaker on; a plug-in tester should read "correct".
No ground wire in the box? A 3-prong outlet needs one. Put in a GFCI instead and stick on its "No equipment ground" label (CPSC; NEC 406.4(D)(2)).
Stop and call an electrician
- Wires that test live with the breaker off: stop and call an electrician (Leviton).
- Aluminum wire (dull silver, or "AL" on the cable): a fire risk at outlets and switches, don't touch it yourself (CPSC).
- Cloth-covered wires on porcelain knobs or tubes (knob-and-tube).
- Scorched, melted or brittle insulation, or a plate that's warm to the touch (CPSC).
- A 3-wire cable whose black and red come from two breakers sharing one white (a shared neutral).
- Wires that don't match any of these diagrams, or you can't tell which is which.
- The plug-in tester shows open ground, open neutral or reversed wires on a new outlet: the fault is in the wiring.
From Leviton instruction sheets and product pages, UHMC and EC&M, the CPSC, and the NEC as explained by EC&M, IAEI and JLC. Code years differ by city. · Not yet reviewed by a licensed electrician