How to install a GFCI outlet
The cable bringing power goes on the GFCI's LINE screws: black to brass, white to silver. With one cable in the box, that's all, and the yellow sticker stays on the LOAD screws. With two cables, put the one going on to the next outlets on LOAD to protect them too, or join both cables to LINE with short pigtails to protect only this outlet. If it won't reset, LINE and LOAD are swapped (Leviton). Then press TEST and RESET once a month (CPSC).
One cable
GFCI box
Two cables, protecting the outlets after it
GFCI box
Two cables, protecting only this one
GFCI box
Which cable is LINE?
- Power off. Take one cable's black and white off the old outlet and cap each with a wire nut.
- Put the outlet back, power on: if it works, the capped wires are LOAD; if not, they're LINE.
- Power off again and label both cables before you go on.
Step by step
First
- Turn off the breaker. A wall switch off is not enough. Put tape or a note on the breaker so nobody turns it back on.
- Prove it's dead: check your tester on an outlet you know is live, test every wire in the box, then check the tester on the live outlet again (Klein). A voltage pen alone isn't proof: use a plug-in or two-probe tester where you can.
- Take a photo of the wires before you move any of them.
Then
- Plug a lamp into both halves and turn the breaker off until both are dead (Leviton).
- One cable in the box: it's the LINE. Two cables: find the LINE before you start (below).
- LINE black to the LINE brass screw, LINE white to the LINE silver screw. Leave the yellow sticker on the LOAD screws unless you use them.
- Ground: a short bare or green pigtail from the green screw, joined to the box's ground.
- Breaker on, press TEST (power goes off), then RESET. If it won't reset, LINE and LOAD are swapped (Leviton).
- Using LOAD: press TEST and find every outlet that goes dead. Stick a "GFCI protected" label on each.
- Press TEST and RESET once a month (CPSC).
Where a GFCI is required
The 2023 electrical code's list for homes (NEC 210.8(A), via EC&M):
- Bathrooms
- Garages and accessory buildings
- Outdoors
- Crawl spaces
- Basements
- Kitchens (every outlet since 2023)
- Food and drink prep areas
- Within 6 ft of a sink
- Boathouses
- Within 6 ft of a tub or shower
- Laundry areas
- Damp or wet places indoors
Kitchens used to mean only the outlets serving the counter, and basements only unfinished ones; your city may be on an older code. Replacing an outlet in one of these places means the new one must be GFCI-protected (NEC 406.4(D)).
No ground wire: a GFCI still protects you from shocks. Stick on the "No equipment ground" label that comes with it (CPSC).
Stop and call an electrician
- Wires that test live with the breaker off: stop and call an electrician (Leviton).
- Aluminum wire (dull silver, or "AL" on the cable): a fire risk at outlets and switches, don't touch it yourself (CPSC).
- Cloth-covered wires on porcelain knobs or tubes (knob-and-tube).
- Scorched, melted or brittle insulation, or a plate that's warm to the touch (CPSC).
- A 3-wire cable whose black and red come from two breakers sharing one white (a shared neutral).
- Wires that don't match any of these diagrams, or you can't tell which is which.
- More than four wires in the box (not counting grounds), or a 3-wire cable: the maker says not to put a GFCI there (Leviton).
From the Leviton GFCI instruction sheet and buying guide, the CPSC and EC&M, the CPSC, and the NEC as explained by EC&M, IAEI and JLC. Code years differ by city. · Not yet reviewed by a licensed electrician